Stronghold Fire Doors are manufactured strictly in accordance to SANS 1253:2003 edition 3 specifications for fire doors and fire shutters and will provide a rating of up to two hours. The fire retardant slab (core) sandwiched between various types of wood, steel or laminate is constructed from a reinforced insulated material which acts as a fire retardant in a case of fire. The ironmongery fitted to a fire door is key to the integrity of your fire door and should be fire rated. Non-fire rated ironmongery could cause your door to fail in case of a fire.
.
DESCRIPTION | CLASS A | CLASS B | CLASS C | CLASS D | CLASS E | CLASS F |
---|---|---|---|---|---|---|
Stability | 1 Hour | 2 Hours | 2 Hours | 2 Hours | 1/2 Hour | 1/2 Hour |
Integrity | 1/2 Hour | 1 Hour | 2 Hours | 2 Hours | 1/2 Hour | 1/2 Hour |
Insulation | 1/2 Hour | 1 Hour | N/A | 2 Hours | 1/2 Hour | N/A |
Impact Test | N/A | N/A | Yes | Yes | N/A | N/A |
Stability
The ability to fulfil its design function of keeping an opening closed in the face of fire so that no fissure or opening wider than 25mm develops.
Integrity
Enables a door to resist fire without the development of perpendicular through openings wider than 6mm and longer in total than the largest dimension of the door
Insulation
The ability to prevent the transmission of enough heat to raise the unexposed face temperature but more than 140 degree Celsius above the initial temperature.
Impact Test
Enables the door to resist two successive impacts of a sandbag 250mm in diameter and a mass of 27kg without the formation of any opening wider than 25mm. For further details the test is fully described in The South African National Standard
Total Door Solution
Our sales team are experienced to cover all aspects of the design and construction of your fire doors; from ensuring correct door and ironmongery specification, through manufacture, installation and successful project completion.
Adaptability & Flexibility
Our capacity to adapt to customer needs has been a significant factor in our success. We understand that not all projects are the same. Our door solutions are tailor made to meet your requirements and ensure full regulatory compliance.
Quality & Durability
With many years of knowledge in specialist bespoke door systems, we have come to realise that the strength and durability of a fire door, lies within the pre-assembly preparation. Reinforcing the core and strategically inserting various preps to take ironmongery is paramount to the longevity of our doors.
Elements
Standard fire door finishes will not stand up to harsh environments and therefore, needs to be protected to prolong the life of your door. All external doors must be cladded with Galvanised or Stainless Steel Sheeting and full surround channel to protect the edges.
How to Determine the Handing of Your Fire & Escape Doors
Handing refers to the direction of the door swing as it is opened.
Your Door Handing is always determined from the PULL side which is also the side where the Hinge Knuckles are visible.
Door Handing for Single Doors
If you use your Left hand to pull the door towards you – Left Hand
If you use your Right hand to pull the door towards you – Right Hand
Door Handing for Double Doors
Double Doors have an Active Leaf and a Passive Leaf. When ordering doors always refer to the handing of the active leaf.
If you use your Left hand to pull the active leaf towards you – Left Hand Active
If you use your Right hand to pull the active leaf towards you – Right Hand Active
NOTE:
It is difficult to change the handing of your door once it is hung or installed therefore, its important that we get this right. Fire & Escape Door must always open towards the direction of escape, there are however exceptions and when doors are opening in, it will not affect how you order your doors, but it will affect how we need to install the ironmongery. Ironmongery will always be fitted for doors opening out, unless otherwise specified.
Complete Door Solution Specials
The ability to prevent the transmission of enough heat to raise the unexposed face temperature but more than 140 degree Celsius above the initial temperature.